Voltage Drop: Why Long Wires Lose Power
Understand why electricity loses pressure over long distances. Learn how wire gauge and material affect voltage drop, and use our free calculator.
Related Calculator
Use the Voltage Drop Calculator | DC, 1-Phase & 3-Phase AC Wire Loss Solver to apply what you learn in this guide.
On this page
No practical conductor has zero resistance. Every foot of copper or aluminum wire introduces finite electrical impedance (R) that converts a portion of electrical pressure into waste heat as current flows, lowering the voltage available at the far end of the run—a phenomenon known as voltage drop (V_drop).
Over short interior runs, voltage drop is negligible. Over long outdoor trench runs, subpanel feeders, or low-voltage DC solar arrays, excessive drop dims lighting, triggers electronics brownouts, and forces motors to overheat while pulling compensatory current. You can evaluate conductor gauge, material, distance, and load current immediately with our Voltage Drop Calculator.
Core Equations: Single-Phase, Three-Phase, and AWG Geometry
In DC and single-phase AC branch circuits (12–14 AWG through 6 AWG, where inductive reactance is minor), voltage drop is governed by Ohm's Law (V_drop = I × R_loop) across the full out-and-back conductor path (2 × L):
V_drop (1φ / DC) = (2 × K × I × L_ft) / CM
V_drop (3φ AC) = (1.732 × K × I × L_ft) / CM
%V_drop = (V_drop / V_source) × 100%
Here, I is load current (A), L_ft is one-way run distance (ft), CM is the conductor's cross-sectional area in circular mils, and K is the material's specific resistance (Ω·CM/ft) at the operating temperature (75 °C standard rating):
- Copper (
Cu) at 75 °C:K ≈ 12.9 Ω·CM/ft(ρ = 1.68 × 10⁻⁸ Ω·mat20 °C) - Aluminum (
Al) at 75 °C:K ≈ 21.2 Ω·CM/ft(ρ = 2.82 × 10⁻⁸ Ω·mat20 °C)
In balanced three-phase AC circuits, the round-trip factor of 2 is replaced by √3 (1.732), reflecting 120° phase symmetry across the three line conductors.
Step-by-Step Worked Example: 150-Foot Detached Workshop Run
Suppose you are wiring a 120 V, 15 A branch circuit to a detached workshop L = 150 ft one-way from the main breaker panel using 75 °C-rated copper (K = 12.9). Although 14 AWG or 12 AWG copper meets ampacity limits for 15 A, let us check voltage drop against the NEC 3% (3.60 V) branch guideline:
- Test
12 AWGCopper (6,530 CM):V_drop = (2 × 12.9 × 15 A × 150 ft) / 6,530 CM = 58,050 / 6,530 = 8.89 V%V_drop = (8.89 V / 120 V) × 100% = 7.41%— Fails (111.11 Vdelivered; more than double the3%target). - Test
10 AWGCopper (10,380 CM):V_drop = 58,050 / 10,380 = 5.59 V%V_drop = (5.59 V / 120 V) × 100% = 4.66%— Still exceeds3.0%(114.41 Vdelivered). - Test
8 AWGCopper (16,510 CM):V_drop = 58,050 / 16,510 = 3.52 V%V_drop = (3.52 V / 120 V) × 100% = 2.93%— Passes (116.48 Vdelivered, comfortably inside3.0%). - Evaluate Doubling Voltage to
240 V(1,800 Wat7.5 A) on12 AWG:V_drop = (2 × 12.9 × 7.5 A × 150 ft) / 6,530 CM = 29,025 / 6,530 = 4.44 V%V_drop = (4.44 V / 240 V) × 100% = 1.85%Switching to240 Vhalves current and doubles the reference voltage, reducing percentage voltage drop by4×(7.41%down to1.85%) using thinner12 AWGwire.
Copper AWG Voltage Drop Benchmarks (15 A, 120 V Single-Phase, 75 °C)
Each decrease of three AWG numbers roughly doubles conductor cross-sectional area (CM) and halves DC resistance. The benchmarks below use K = 12.9 Ω·CM/ft for a 15 A load at 120 V.
| Wire Gauge (AWG) | Cross-Section (CM / mm²) | Max 3% Run (ft, 15 A @ 120 V) | Drop at 100 ft (V) | Drop % at 100 ft | Common Wiring Application |
|---|---|---|---|---|---|
| 14 AWG | 4,110 CM (2.08 mm²) |
38.2 ft |
9.42 V |
7.85% |
Short interior 15 A lighting circuits |
| 12 AWG | 6,530 CM (3.31 mm²) |
60.7 ft |
5.93 V |
4.94% |
Standard 20 A interior receptacles |
| 10 AWG | 10,380 CM (5.26 mm²) |
96.6 ft |
3.73 V |
3.11% |
Medium outdoor runs, 30 A dryers |
| 8 AWG | 16,510 CM (8.37 mm²) |
153.6 ft |
2.34 V |
1.95% |
Long 120 V shed circuits, 40 A ranges |
| 6 AWG | 26,240 CM (13.30 mm²) |
244.1 ft |
1.47 V |
1.23% |
Detached garage subpanels, EVSE lines |
| 4 AWG | 41,740 CM (21.15 mm²) |
388.3 ft |
0.93 V |
0.77% |
Long-distance 100 A service feeders |
Regulatory Thresholds, AC Impedance, and Design Pitfalls
To keep installations safe, code-compliant, and reliable under full load, verify four critical field constraints before pulling wire:
- NEC Guidelines vs. Mandatory Limits: Under
NEC 210.19(A)Informational Note No. 4 and215.2(A)(1), the3%branch /5%combined drop limits are engineering recommendations—except where local codes enforce them or specific articles apply (such as fire pumps underNEC 695.7, capped at15%starting drop). - AC Reactance in Heavy Feeders (
> 2 AWG): Below4 AWG, DC resistance dominates. Above2 AWGin AC feeders, inductive reactance (X_L, higher in steel conduit than PVC) raises total impedance (Z = R × cos φ + X_L × sin φ); verify large runs against NEC Chapter 9 Table 9. - Terminal Lugs After Upsizing: Oversized
8 AWGor6 AWGconductors pulled for voltage drop may not fit15 A/20 Abreaker or receptacle lugs. Transition via listed splices inside a junction box to short12 AWGpigtails, and upsize the equipment ground perNEC 250.122(B). - Low-Voltage DC and Extension Cord Traps: Stringing
200 ftof16 AWG(2,580 CM) extension cord for a12 Asaw drops(2 × 12.9 × 12 × 200) / 2,580 = 24.0 V(20%), starving the motor at96 Vand melting plugs. Similarly,12 V–24 Voff-grid solar circuits demand heavy6–2/0 AWGcable.
Frequently Asked Questions
What is the maximum acceptable voltage drop under NEC guidelines?
NEC Informational Notes 210.19(A) and 215.2(A)(1) recommend limiting voltage drop to 3% on any single branch circuit or feeder, and 5% combined from the service panel to the furthest outlet. For a 120 V branch circuit, 3% equals 3.6 V (delivering at least 116.4 V).
Why do you multiply wire length by 2 in single-phase voltage drop formulas?
In DC and single-phase AC circuits, current travels out to the load along the hot (or positive) conductor and returns along the neutral (or negative) conductor. Total resistive path length is therefore twice the one-way distance between panel and equipment.
What happens to a motor or power tool when voltage drops too far?
Induction and universal motors attempt to maintain mechanical torque by drawing higher current as supply voltage sags. Under-voltage increases motor winding temperature (I² × R heating), slows startup acceleration, trips thermal overloads, and risks permanent insulation damage.
How much larger must aluminum wire be compared to copper for the same voltage drop?
Electrical-grade aluminum has roughly 61% the conductivity of copper (resistivity 1.64× higher). To match the voltage drop of copper over identical distance and load, installers typically upsize by two American Wire Gauge (AWG) steps—for example, using 4 AWG aluminum in place of 6 AWG copper.
Why is voltage drop far more critical in 12 V DC solar and RV wiring than in 120 V AC?
Percentage drop scales inversely with system voltage. Losing 1.2 V along a cable is only a 1% drop on a 120 V AC circuit, but on a 12 V battery bank it represents a 10% voltage collapse—enough to trigger low-voltage inverter shutdowns and prevent refrigerators from starting.